Number |
Project Name |
Unit |
Technical Parameter |
|
1 |
Rated voltage |
kv |
10 |
|
2 |
Maximum operating voltage |
kV |
12 |
|
3 |
Rated frequency |
Hz |
50 |
|
4
|
1min power frequency withstand voltage |
W |
Phase to phase and phase to ground 42, isolation fracture 48 |
|
5 |
Lightning impulse withstand voltage |
W |
Phase to phase and phase to ground 75, isolation fracture 85 |
|
6 |
Rated current of main busbar |
A |
630 |
|
7 |
load switch |
Rated current |
A |
630 |
8 |
Mechanical life |
second |
5000 |
|
9 |
Breaking no-load transformer capacity |
KNA |
1250 |
|
10 |
Rated thermal stability current |
MA |
20(4S) |
|
11 |
Rated dynamic stable current |
kA |
50(Peak value) |
|
12 |
Rated making current |
A |
50(1Peak value) |
|
13 |
combination electrical equipment |
Maximum rated current of fuse |
A |
100 |
14 |
Rated transfer current |
A |
1500(2000) |
|
15 |
Rated short-circuit breaking current |
kA |
31.5 |
|
16 |
Distribution fuse model |
|
SOLAJ-12(XRNTO-10) |
|
17 |
Maximum rated capacity of matched transformer |
kVA |
1250 |